Products

For product inquiries please contact your local representative.

SHARE THIS

Overview

The Price Pressure Control Valve (PCV) is designed as a pressure control valve to regulate duct pressure in a Pressure Independent or Pressure Dependent system.

The PCV uses either a field calibrated electric or PIC DDC controller to ensure that over or under pressurization of the duct will not occur.

Typical Applications
The PCV can be used as either a bypass unit or as a throttling device

In the bypass application, static pressure is normally measured 2/3 down the longest duct run. The PCV will bypass main supply air to a plenum or air handler return to maintain duct static pressure at a constant setting.

In the throttling (or downstream) application, placing a static pressure sensor downstream of a PCV unit will allow for control of the pressure supplied to the VAV diffusers. The control valve is designed to maintain duct static pressure through adjustment of a control damper.

Construction PCV

  • Rectangular ducts constructed of 22 gauge zinc-coated steel.
  • Round ducts constructed of 24 gauge zinc-coated steel.
  • Damper fabricated from 22 gauge zinc-coated steel, mechanically fastened.
  • Damper shaft, sensor and all fasteners exposed to airflow are type 304 stainless steel.
  • Damper shaft bearings and damper gasket are polyethylene.
  • Controller cover and all external metal components are zinc-coated steel.
  • SP300 sensor.

Sequence of Operation – Constant pressure, bypass

  • On an increase in duct static pressure the controller/actuator will open the VAV damper to increase the amount of air bypassed.
  • On a decrease in duct static pressure the controller/actuator will close the VAV damper to reduce the amount of air bypassed.
  • Duct static pressure is held constant.

 